Ducati RS 485 Bedienerhandbuch Seite 9

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 15
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 8
DO NOT CHANGE THIS PARAMETER IF THE CONTROLLER
IS INSTALLED ON A DUCATI ENERGIA POWER FACTOR
CORRECTION SYSTEM.
DATA
“IL”
“IL”
IL IL IL
DATA
“COn”
“COn”
DO NOT CHANGE THIS PARAMETER IF THE
CONTROLLER S INSTALLED ON A DUCATI ENERGIA
POWER FACTOR CORRECTION SYSTEM.
DATA
“SUP”
“SUP” “U2”
U1 U2
DO NOT CHANGE THIS PARAMETER IF THE
CONTROLLER IS INSTALLED ON A DUCATI ENERGIA
POWER FACTOR CORRECTION SYSTEM.
DATA
“FAS”
“FAS”
On blo
DO NOT CHANGE THIS PARAMETER IF THE
CONTROLLERS INSTALLED ON A DUCATI ENERGIA
POWER FACTOR CORRECTION SYSTEM.
“ACq”
“ACq” no
DATA
no
Press to go on to the next parameter
10.4 = Mains C.T. ratio.
The parameter is displayed in turn with the value
previously set by the user.
The value can be changed using the or key.
Setting examples:
C.T. 300/5 =60; C.T. 350/5 =70; C.T. 400/5 =80
Ex.
Press to go on to the next parameter
10.5 = Type of connection of controller to mains.
is displayed in turn with the default value “FF1”.
The user can change this parameter using the or key
(possible settings: FF1, FF2, F-n - see chap 5 - Page 59).
Press to go on to the next parameter
10.6 = Setting of terminal used to power the controller.
is displayed in turn with the default value .
The user can change this parameter using the or key
(possible settings: /230V, /400V).
Press to go on to the next parameter
10.7 =Activation or deactivation of automatic adjustment
of mains C.T. direction.
is displayed in turn with the default value “0n”
(autoadjustment enabled).
The parameter can be changed using the or key
(possible settings: /auto-adjustment, /C.T. direction
fixed).
10.8 = Menu for launching the procedure for acquiring the
power of single steps and setting their switching logic.
is displayed in turn with the default value ”.
The parameter can be changed using the or key and
confirming by pressing ; the possible settings are:
= no acquisition procedure will be carried out.
AUt
“C1”
DATA
DATA
Pr
Pro
PFC
DATA
SWITCHING LOGICS
LINEAR LOGIC
GEOMETRIC LOGIC
= a new automatic acquisition procedure will be carried out.
The capacitor steps will be switched on and measured in
sequence a total of three times each. At the end of this procedure
the controller will alternately display and the measured
power value of the first step; the power of the next step can be
displayed by pressing the key.
Press for three seconds to go on to the next parameter.
= the switching logic & power of the single steps is manually
set.
When the letters “Pro” appear, select the desired program (see
Table 1 - Page 72) using the or key and press DATA to
confirm.
Thereafter, when the letters “PFC” appear, set the value in kVAr
of the first power factor correction capacitor bank (always
connected to output terminal “1”), again using the or key;
Example: if you have an automatic 100kVAr system with power
70 steps of 10-10-20-20-40 the parameters should be set as
follows:
= 26 (see Table 1 - Page 72)
= 10.
Press to confirm and go on to the next parameter.
The controller can adopt one of three logics to switch the
capacitor banks in and out of service in order to achieve and
maintain the set cosphi, i.e.:
This logic is identified by the code 1:1:1 and presupposes the
condition that all capacitor banks have equal powers. Given a
situation such as the one illustrated in the table,
Bank No. 1 2 3 4 5 6
Status OFF ON ON ON OFF OFF
the controller will switch on bank no. 5 if a bank needs to be
switched into service and switch off bank no. 2 if one needs to be
switched off. This will ensure that all the banks will work and as a
result component wear will be evenly distributed among them.
It is identified by the code 1:2:4 and presupposes the condition
that each bank has a power equal to or at most double the power
of the one that precedes it. Assuming that the banks have powers
as shown in the table,
Bank No. 1 2 3 4 5 6
Power 10 20 40 40 40 80
and that the load requires 50 kVAr, the controller will switch on the
1st, 2nd and then 3rd banks, thereby reaching 70 kVAr. At this
point it will switch off the 1st and then the 2nd, which will bring it to
40 kVAr, and finally it will switch the 1st back on to reach 50 kVAr.
As may be observed, this logic makes it possible to obtain a large
number of steps with a limited number of banks. However, the
number of switching operations is not evenly distributed among
the banks, resulting in greater wear on the first ones.
Seitenansicht 8
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15

Kommentare zu diesen Handbüchern

Keine Kommentare