MANUAL
PROGRAMMING
SELF-
ACQUISITION
YES
YES
NO
NO
7
8
5
Simplified Diagram relative to First Powering up
1. POWER THE CONTROLLER
2. DISPLAYALTERNATELY SHOWS “IL”AND “- - -”
3. ENTER “IL” PARAMETER MAINS C.T. RATIO (e.g. w/ C.T. 200/5 enter 40)
4. “+”AND “-” TO CHANGE THE PARAMETER AND “DATA” KEY TO CONFIRM
5. “FAS” DISPLAYED IN TURN WITH “0” OR “1”
6. IS THE CONTROLLER INSTALLED ON ADUCATI ENERGIAPOWER FACTOR CORRECTION SYSTEM?
7. DISPLAYALTERNATELY SHOWS “COS”AND THE SYSTEM POWER FACTOR
8. STEPS SWITCHED INAND OUT OF SERVICE TOACHIEVE DESIRED POWER FACTOR
9. STEPS SWITCHED INAND OUT THREE TIMES (AUTO-ACQUISITION)
10. DISPLAYALTERNATELY SHOWS “C1”AND THE VALUE MEASURED FOR THE FIRST BANK
11. PRESS “DATA” KEY TO DISPLAY VALUE OF SUBSEQUENT BANKS
12. ARE THE MEASURED POWERS CORRECT?
13. PRESS THE “DATA” KEY THREE TIMES TO EXIT
14. STARTA NEW SELF-ACQUISITION OR CARRY OUTA MANUAL PROGRAMMING
15. TO LAUNCHA NEW AUTO-ACQUISITION PROCEDURE PRESS “ALARM/ RESET” + “+”
16. FOR MANUAL PROGRAMMING PRESS ALARM/RESET” +“-”
17. DISPLAY SHOWS “Pro” PRESS “+” OR “-” TO SET THE DESIRED PROGRAM (SEE TABLE 1 - PAGE 72)
18. PRESS THE “DATA” KEY
19. DISPLAY SHOWS “PPC” PRESS “+” OR “-” TO SET THE VALUE OF THE FIRST BANK
20. PRESS THE “DATA” KEY