press or to choose the status of the relay you want to set in
the manual operating mode; press the key to display the
status of the subsequent relay. After viewing the status of the last
relay, press the key to exit this function.
Press to access the relevant menu (“ ” will appear
on the display and will flash);
when the key is pressed, REGO will alternately display “ ”
and the value in kVAr associated with the first step.
Ex.
Every time you press the key, the controller will show the
powers of the individual steps in sequence; after viewing the last
step press the key to exit this function.
Press to access the menu pertaining to the procedure
for checking the powers of the capacitor steps (the display will
show “ ” and will flash).
Pressing the key will cause REGO to switch off all the banks
and start the procedure for measuring the power of all the steps
(the cycle will be launched three times to provide a better
measurement). If REGO detects differences of more than 25% in
the power that was associated with the step during the previous
auto-acquisition procedure, the corresponding LED will flash. At
the same time the letters “ ” will appear on the display
and the user must disable the step by pressing ; if
this key is not pressed within a few seconds, the operation will be
terminated without any effect taking place. Once the check is
completed, REGO will function as before, with the exclusion of
any steps detected to be faulty, whose LEDs will continue flashing
to signal their status of unavailability.
The user can decide which relays the controller must not use in
the automatic mode.
Press + to access the menu for enabling/disabling
the output relays (the display will show “ ” and will flash).
When you press the key, the + LEDs will flash and the
display will start showing the status of the first relay: “ ” will be
displayed in turn with its status (“ ” or “ ”).
Ex.
At this point you can choose the status of the relay, pressing the
key to switch it “ ” or the key to switch it “ ”. Press the
key to display the status of the next relay; after viewing the
status of the last relay, press the key to exit this function.
DATA
DATA
12.2 DISPLAYING THE POWERS OF SINGLE STEPS
DATA + CP
C1
DATA
DATA
12.3 PROCEDURE FOR CHECKING THE EFFICIENCY OF
THE SINGLE STEPS
DATA +
ChP
rSt
ALARM/RESET
12.4 PROCEDURE FOR ENABLING/DISABLING OUTPUT
RELAYS IN THE AUTOMATIC OPERATING MODE
AUTO/MAN
Abi
r1
On OFF
On OFF
DATA
DATA
12.5 DISPLAYING THE COUNTER OF TOTAL OPERATIONS
PERFORMED BY EACH RELAY
AUTO/MAN
Cnt”
C1
.
DATA
DATA
Important:
12.6 DISPLAYING THE SOFTWARE RELEASE
ALARM/RESET + DATA
12.7 PROCEDURE FOR TESTING CONNECTIONS TO
CAPACITOR STEPS
K
tSt AUTO/MAN
AUTO/MAN
12.8 GENERATOR POWER FACTOR CORRECTION MODE
AUTO/MAN
Inu On OFF
The user can display the number of switching operations
performed by each relay controlling the capacitor banks.
Press + to access the relevant menu (the display
will show “ and will flash).
When you press the key, the + LEDs will flash and the
display will show the operation performed by the first output relay.
“ ” will appear, followed by the number of switching operations.
A“ ” is used to separate thousands.
Ex.
Press the key to display the number of switching
operations of the next relay; after viewing the data of the last
relay, press the key to exit the function.
when an output relay counter totals over 100,000
switching operations, the LED corresponding to the step will flash
to warn of the need to overhaul/replace the contactors. The
output will not be disabled, only a warning will be signaled.
To display the software release number of the controller, press
: the display will alternately show “Flr”
and the firmware version “x.xx”.
An automatic procedure is provided to make it easier to check the
efficiency of connections to the capacitor steps, independently of
the mains network status and the presence of current on
terminals “ ” ed “L”. This procedure can be launched by pressing
DATA + AUTO/MAN regardless of the current controller situation
(“ ” will appear on the display and the LED will
flash);
if the procedure is launched during normal operation, it will be
necessary to press the key for about another 2
seconds to confirm the launching of the test. The procedure
consists in switching on the individual steps in sequence at two-
second intervals. The closing time of an individual step is five
seconds.
To correct the power factor of the generators, the user must set
this operating mode, which involves inhibiting the automatic
mains CT direction adjustment function and configuring the
signals accordingly.
This operation must be carried out with the mains powered by the
generator.
Press + to access the menu for fixing the C.T.
direction. When you press the keys, the LED will flash and
you must press the corresponding key. At this point the and
LEDs will flash and the controller will simultaneously display
“ ” (INV) in turn with “ ” or “ ”.