Parameter Description Range Default
Fr
COS 0.95
UFF 400
IL
Con FF1
SUP
U2
FAS
On
ACq
no
s:s:s:
Table 2: Setup parameters
(10.1) Measured mains 50 or 60 Hz -/-
Freq. only an indication
(10.2) Power factor to be 0.8IND ÷
achieved within the system 0.8CAP
(10.3) Voltage rating of controller 230 or 400
(10.4) Mains C.T. ratio. 1...3000
Eg: with CT100/5 set 20
Eg: with CT200/5 set 40
(10.5) Type of connection FF1
of controller to mains. FF2
F-n
(10.6) Setting of terminal used U1 (230V)
to power the controller. U2 (400V)
(10.7) Auto-adjustment of
mains C.T. direction:
On=auto-adjustment On
blo= fixed direction blo
(10.8) Acquisition of step power:
no = no acquisition
procedure no
AUt=automatic acquisition Aut
Pr = manual setting Pr
(10.9) Display of set logic 1:1:1 -/-
1:2:2
1:2:4
11) DISPLAY OF MEASUREMENTS
C.O.S. -.-.-.
DATA
“COS”
“UFF”
“IL”
“PA”
“PL”
“thd”
“C
12) ADDITIONAL FUNCTIONS
12.1 MANUAL OPERATING MODE
AUTO/MAN
r1 On OFF
Normally the display shows the system cos..
Aminus sign indicates a capacitive power factor.
N.B.: In the event of a power cut, the controller will not be able to
calculate the cos phi and will alternately display & ”.
Press the key to display the measurement readings: every
time you press, the next parameter will be displayed.
The parameters are displayed in the following sequence:
(system power factor)
(effective measured line voltage)
(line current measured at the primary winding of the CT)
(equivalent active power absorbed by load, in kW)
(equivalent reactive power absorbed by load, in kVAr)
(crest factor normalized to 1: values less or greater than
1 if harmonic distortion is present)
(temperature inside panel board enclosure at the point
where the controller is installed; the value shown may be
considered reliable after about 1 hour of operation)
Press the key until the
corresponding LED lights up: the controller is now ready to be
programmed in the manual mode.
The user must indicate the desired status for every output relay:
at the end of the programming procedure, the controller will set all
the capacitor steps in the status requested. Operatively, REGO
indicates
in turn with the status (which can be or ”);
Ex.
o
for about two seconds
SEMI-GEOMETRIC LOGIC
IMPORTANT
first
s:s:s:
DATA
DATA
IMPORTANT: If the controller is installed on a DUCATI
ENERGIA power factor correction system, we advise the user
not to change the default parameters (See Table 2 - Page 74).
It is identified by the code 1:2:2 and the power of the first bank
must be half that of the others, which must all be equal. The first
bank is managed according to a geometric logic whereas all the
others, which have equal powers, are managed according to a
linear logic.
: the first output relay must always be connected to
the capacitor bank with the least power. If the powers of the steps
are all equal, only make sure that the first step is not left without
controlled capacitors. Moreover, in the event that a specific user
program is configured (as in Table 1), the value of the bank
must be set.
10.9 = Display of set logic At the end of an automatic
acquisition or manual setting procedure, the controller will
display a switching sequence and 72 will start to work
automatically. If the controller cannot identify an optimal
sequence, it will set the 1:1:1 logic.
Ex.
Press to go back to the first parameter in the menu. To
exit the setup menu, keep the key pressed down for
three seconds
Program Sequence OF DESCRIPTION
Setting of of
Pr1 1:1:1 2 steps and power of
bank connected to the
first output relay.
Pr2 1:1:1 3
Pr3 1:1:1 4
Pr4 1:1:1 5
Pr5 1:1:1 6
Pr6 1:1:1 7
Pr7 1:1:1 8
Pr8 1:1:1 9
Pr9 1:1:1 10
Pr10 1:1:1 11
Pr11 1:1:1 12
Pr12 1:2:2 2
Pr13 1:2:2 3
Pr14 1:2:2 4
Pr15 1:2:2 5
Pr16 1:2:2 6
Pr17 1:2:2 7
Pr18 1:2:2 8
Pr19 1:2:2 9
Pr20 1:2:2 10
Pr21 1:2:2 11
Pr22 1:2:2 12
Pr23 1:2:4 2
Pr24 1:2:4 3
Pr25 1:2:4 4
Pr26 1:2:4 5
Pr27 1:2:4 6
Pr28 1:2:4 7
Pr29 1:2:4 8
Pr30 1:2:4 9
Pr31 1:2:4 10
Pr32 1:2:4 11
Pr33 1:2:4 12
Table 1: User programs (selection of SEQUENCE and OF
STEPS)